Eaton NZM4 3P Circuit Breaker 1200A 50kA UL/IEC - 271141
Notice: This product will be discontinued in the future
The Eaton Industries MCCB power circuit breaker is designed for a nominal continuous current of 1200A and nominal voltage of 690V. It offers a nominal interruption capacity of 37kA at 400V, with an overload setting range of 1200A. The MCCB also offers a short-time delay range of 2400 - 12000A, and an instantaneous short-circuit range of 2400 - 14400A. It is a 3 pole circuit-breaker with a switching capacity of 42 kA at 480V, and 35 kA at 600V. The unit is designed for fixed installations, featuring screw connections and compliance with UL/CSA and IEC standards. Its protection functions are tailored for systems, cables, selectivity, and generator protection.
Notice: This product will be discontinued in the future
Description
The Eaton Industries MCCB power circuit breaker is designed for a nominal continuous current of 1200A and nominal voltage of 690V. It offers a nominal interruption capacity of 37kA at 400V, with an overload setting range of 1200A. The MCCB also offers a short-time delay range of 2400 - 12000A, and an instantaneous short-circuit range of 2400 - 14400A. It is a 3 pole circuit-breaker with a switching capacity of 42 kA at 480V, and 35 kA at 600V. The unit is designed for fixed installations, featuring screw connections and compliance with UL/CSA and IEC standards. Its protection functions are tailored for systems, cables, selectivity, and generator protection.